• DocumentCode
    3503542
  • Title

    An active power filter for protective relaying at EHV line

  • Author

    Kumar, Parmod ; Mahajan, Alka ; Singh, Bhim

  • Author_Institution
    Dept. of Electr. Eng., Delhi Coll. of Eng., India
  • Volume
    2
  • fYear
    1999
  • fDate
    36495
  • Firstpage
    895
  • Abstract
    Nonsinusoidal voltages and currents affect the performance of protective relays under normal as well as fault conditions. The intent of this paper is to present an active power filter for relaying operations. The active power filter provides harmonics-free voltage and current signals to the relay, thereby ensuring its designed performance. Combined shunt and series active power filters are used to filter out the voltage as well as current harmonics from the input signal to the relay. Simulation studies for a single phase to earth fault on a 220 kV transmission line have been presented
  • Keywords
    active filters; power harmonic filters; power system harmonics; power system relaying; power transmission faults; power transmission lines; power transmission protection; relay protection; 220 kV; EHV line; active power filter; fault conditions; normal conditions; protective relaying; shunt/series active power filters; single-phase to earth fault; Active filters; Earth; Power harmonic filters; Power system harmonics; Power transmission lines; Protection; Protective relaying; Relays; Signal design; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    TENCON 99. Proceedings of the IEEE Region 10 Conference
  • Conference_Location
    Cheju Island
  • Print_ISBN
    0-7803-5739-6
  • Type

    conf

  • DOI
    10.1109/TENCON.1999.818563
  • Filename
    818563