Lightning outages calculations for transmission lines
Author
Torres, Carlos Romualdo
Author_Institution
Inst. de Investigaciones Electr., Mexico
Volume
2
fYear
1999
fDate
1999
Firstpage
185
Abstract
The study of the lightning performance of transmission lines is conducted in this work by using statistical and analytical methods in order to predict shielding failure and backflashover rates. The incidence of lightning strokes on transmission lines is calculated by using the electrogeometrical model. Lightning overvoltage calculations are made by using a multiphase conductor travelling wave method, in order to determine the effect that the rise time has on the tower top potential, as well as for different grounding resistances. A simple model, for backflashover calculations, is considered in the program, as recommended by IEEE Working Groups. Predicted 115 kV transmission line results are compared to field observations showing good correlation
Keywords
power overhead lines; 115 kV; Lightning overvoltage calculations; analytical methods; backflashover calculations; backflashover rates; computer simulation; electrogeometrical model; grounding resistances; lightning outages calculations; multiphase conductor travelling wave method; power transmission lines; rise time; shielding failure; statistical methods; tower top potential;