Title :
Aging characteristics of power transformer oil and development of its analysis using KSOM
Author :
Ji, Pyeong-Shik ; Lim, Jae-Yoon ; Lee, Jong-Pil
Author_Institution :
Dept. of Electr. Eng., Chungju Univ., South Korea
Abstract :
In power systems, substation facilities have become too complex and large according to the extended power system. Also, some facilities become old and often break down unexpectedly. In order to improve the security of the transformer in substation facilities, the development of a transformer diagnosis technique is needed. In this paper, we developed a method to analyze the origin and degree of aging by KSOM based on the dissolved gases in a power transformer. KSOM can perform topological mapping for the multi-dimensional pattern based on the dissolved gases to two-dimensional plane. The possibility and degree of aging for a normal transformer are presented using the proposed quantitative criterion. Furthermore, the aging process of the transformer is analyzed based on the proposed criterion of a special transformer. To demonstrate the validity of the proposed method, a case study is performed and its result is presented
Keywords :
ageing; chemical analysis; chemical variables measurement; insulation testing; power engineering computing; power transformer insulation; power transformer testing; transformer oil; transformer substations; KSOM; aging characteristics; dissolved gas analysis; extended power system; multi-dimensional pattern; power systems; power transformer oil; substation facilities; topological mapping; transformer diagnosis technique; two-dimensional plane; Aging; Dissolved gas analysis; Equations; Gases; Oil insulation; Petroleum; Power system analysis computing; Power system security; Power transformer insulation; Power transformers;
Conference_Titel :
TENCON 99. Proceedings of the IEEE Region 10 Conference
Conference_Location :
Cheju Island
Print_ISBN :
0-7803-5739-6
DOI :
10.1109/TENCON.1999.818596