Lightning stroke attachment characteristics of a covered conductor and a bare conductor on power distribution lines
Author :
Yokoyama, Shigeru ; Asakawa, Akira ; Hashimoto, Yosuke ; Moro-Oka, Yasunari
Author_Institution :
Central Res. Inst. of Electr. Power Ind., Tokyo, Japan
Abstract :
Experimental studies were carried out on the discharge characteristics of a rod-bare conductor gap and a rod-covered conductor gap up to 3 meters. 50% flashover voltage of a rod-covered conductor gap is higher than that of a rod-bare conductor gap under negative impulse voltages. These effects become so notable as the insulated part of a covered conductor is thicker. Measurement using ALPS shows that development of an upward leader from an covered conductor is suppressed by the insulated part of a covered conductor
Keywords :
power distribution lines; ALPS measurements; bare conductor; covered conductor; discharge characteristics; flashover voltage; lightning stroke attachment characteristics; negative impulse voltages; power distribution lines; rod-bare conductor gap; rod-covered conductor gap; upward leader development suppression;