DocumentCode :
3510084
Title :
Evaluation of steady-state and dynamic performance of a synchronized phasor measurement unit
Author :
Gurusinghe, Dinesh Rangana ; Rajapakse, A.D. ; Narendra, Krish
Author_Institution :
Dept. of Electr. & Comput. Eng., Univ. of Manitoba, Winnipeg, MB, Canada
fYear :
2012
fDate :
10-12 Oct. 2012
Firstpage :
57
Lastpage :
62
Abstract :
It is critically important to understand steady-state and dynamic performance of phasor measurement units (PMUs) to ensure reliable and secure operation of the synchrophasor based wide area monitoring, control, and protection systems. The recently published IEEE Standard C37.118.1 provides necessary guidelines to characterize both steady-state and dynamic performance of a PMU. This paper presents a performance evaluation methodology according to the IEEE Standard C37.118.1 and discusses the practical issues in the test environment. Results of the steady-state and dynamic responses tests on an actual PMU are also presented. The PMU performance evaluation approach of this paper is simple, repeatable, and can be performed at any facility with commonly available standard signal playback equipment. The method is based upon using test signals that are mathematically generated from a signal model and play backed into the PMU with precise global position system (GPS) synchronization.
Keywords :
Global Positioning System; IEEE standards; phasor measurement; power system protection; power system reliability; power system security; IEEE standard C37.118.1; PMU performance evaluation approach; dynamic performance evaluation; global position system synchronization; phasor measurement units; precise GPS synchronization; precise global position system synchronization; signal model; standard signal playback equipment; steady-state evaluation; synchronized phasor measurement unit; synchrophasor reliable operation; synchrophasor secure operation; test signals; wide area control; wide area monitoring; wide area protection systems; Distortion measurement; Frequency measurement; Frequency modulation; Interference; Phasor measurement units; Steady-state; Vectors; Discrete Fourier transform; finite impulse response; global position system (GPS); phasor measurement unit (PMU); playback device; step response; total vector error (TVE);
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Power and Energy Conference (EPEC), 2012 IEEE
Conference_Location :
London, ON
Print_ISBN :
978-1-4673-2081-8
Electronic_ISBN :
978-1-4673-2079-5
Type :
conf
DOI :
10.1109/EPEC.2012.6474980
Filename :
6474980
Link To Document :
بازگشت