Title :
Philosophy of Protection for The Macagua-Callao-Claritas 400 kV Line
Author :
Pineda, H. ; Flores, J.L.
Author_Institution :
Transmission Protection Maintenance Dept., EDELCA, Puerto Ordaz
Abstract :
In order to protect in case of fault on the Macagua-Callao-Claritas 400 kV line that supply energy to Eletronorte utilities in Brazil, a particular protection scheme was designed under a fault detection table, which allowed to evaluate the different scenarios in case of the internal and external fault. This scheme are made up of relays of distance and directional overcurrent in the three substations (Macagua-Callao-Claritas), operating in a special permissive overreach scheme with weak infeed, using an optical fiber connection as communication way between each terminal for teleprotection equipments to send and receive the necessary permissive signals to active the scheme. Additionally, for transient faults, the scheme has a single phase auto reclosing which increases the continuity of service of our customer Eletronorte in Brazil
Keywords :
electricity supply industry; fault diagnosis; overcurrent protection; power system interconnection; power transmission faults; power transmission lines; power transmission protection; relay protection; 400 kV; Brazil; Eletronorte utilities; Macagua-Callao-Claritas line protection; directional overcurrent; distance overcurrent; external fault; fault detection; internal fault; optical fiber connection; relays; single phase auto reclosing; special permissive overreach scheme; teleprotection equipments; transient faults; Circuit faults; Earth; Electrical fault detection; Fault currents; Fault detection; Logic; Optical fibers; Protective relaying; Substation protection; Voltage; Fault current; Logic; Protective relaying; Reliability;
Conference_Titel :
Transmission & Distribution Conference and Exposition: Latin America, 2006. TDC '06. IEEE/PES
Conference_Location :
Caracas
Print_ISBN :
1-4244-0287-5
Electronic_ISBN :
1-4244-0288-3
DOI :
10.1109/TDCLA.2006.311570