Title :
Analysis of errors in the measurement of chopped impulses
Author :
Gobbo, R. ; Pesavento, G.
Author_Institution :
Dept. of Electr. Eng., Padova Univ., Italy
Abstract :
IEC 60-2 with its new approach to the qualification of industrial measuring systems covers also the case of chopped LI (lightning impulses), with time to chopping down to 500 ns. The paper discusses the procedure for the possible qualification of a reference measuring system in terms of the parameters of the USR, the sources of error and their dependence on the actual waveform: the influence of the shape of the voltage collapse depending upon the way in which the chopping action is obtained is also discussed
Keywords :
lightning; 500 ns; HV measurement; IEC 60-2; LV measurement; USR parameters; chopped lightning impulses; chopping action; industrial measuring systems qualification; measurement errors analysis; reference measuring system; voltage collapse shape;
Conference_Titel :
High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
Conference_Location :
London
Print_ISBN :
0-85296-719-5
DOI :
10.1049/cp:19990497