Abstract :
A general purpose Emergency Generator Set (EGS) is considered for a methodological study and related reliability behaviour is analyzed. In particular in a procedure of reliability and availability analysis of a EGS, dependent failure events need a complex mathematical model as ??state-space model???? to be a accurately evaluated. Furthermore these dependent failure events are one of the most important reliability characteristic of EGS. This paper suggests a procedure for reliability calculations in presence of dependent failure based on the evaluation of a equivalent failure rate that can be fitted to a network reduction method by simple mathematical calculations. The simplified models analyzed show a good accuracy for a wide range of variation of main reliability characteristics of EGS and utility. The advantages obtained are very useful on reliability evaluation because the possibility of use of network approach provides a shorter route to calculation and it is applicable by a larger number of power system designers.
Keywords :
Availability; Emergency power supplies; Failure analysis; Mathematical model; National electric code; Performance analysis; Power generation; Power system analysis computing; Power system reliability; Safety;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Industrial and Commercial Power Systems Technical Conference, 1995. Conference Record, Papers Presented at the 1995 Annual Meeting., 1995 IEEE
Conference_Location :
San Antonio, TX, USA
Print_ISBN :
0-7803-2479-X
Type :
conf
DOI :
10.1109/ICPS.1995.527002
Filename :
527002
Link To Document :
بازگشت