Abstract
This paper explores the impact of a transmission-line midpoint STATCOM on the performance of the generator loss-of-excitation (LOE) protection. In this context, investigations are conducted on a two-hydrogenerator power station for two LOE contingencies, namely, a complete LOE due to a field-winding short circuit and a partial LOE due to a sudden drop in the excitation voltage at different generator loadings. The results of these investigations show that the midpoint STATCOM has adverse impacts on the LOE distance relay in the form of delay time and/or underreach phenomenon. These adverse impacts vary with the generator loading and the LOE mode. The time-domain simulation studies are conducted using PSCAD/EMTDC software.
Keywords
electric potential; hydroelectric generators; hydroelectric power stations; power generation protection; relay protection; static VAr compensators; time-domain analysis; EMTDC software; LOE distance relay; LOE protection; PSCAD; delay time; excitation protection; excitation voltage sudden drop; field-winding short circuit; generator loadings; generator loss; generator loss-of-excitation protection; hydrogenerator power station; partial LOE; time-domain simulation studies; transmission-line midpoint STATCOM; Automatic voltage control; Generators; Loading; Reactive power; Relays; Trajectory; Transient analysis; Generator loss-of-excitation (LOE) protection; generator steady-state stability limit; generator under excitation limiter; generator underexcited capability limit; static synchronous compensator;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2013.2281581
Filename
6616658
Link To Document