• DocumentCode
    3517945
  • Title

    A Variable N Synchronous Sampling Method for Grid Aperiodic Harmonic Detection and Analysis

  • Author

    Zheng, Hui ; Chen, Zhao ; Peng, Dongkai ; Tang, Tianhao

  • Author_Institution
    Inst. of Electr. Drives & Control Syst., Shanghai Maritime Univ., Shanghai, China
  • fYear
    2010
  • fDate
    26-27 June 2010
  • Firstpage
    42
  • Lastpage
    45
  • Abstract
    This paper proposed a new AC signal detection method based on variable N synchronous sampling to solve the problems on the harmonic detection and analysis of periodic sin waveform in power grid. Comparing with the traditional fixed N synchronous sampling detection in which the number of sampled data is constant in a period, the key difference of the new method is that the period of sampling points as an unknown variable N, to suit for signal detection in the actual situation. Through the acquisition processing and analysis of data detected, the entire period of synchronous sampling could be obtained to overcome the effects of spectral leakage and fence effect.
  • Keywords
    data analysis; discrete Fourier transforms; harmonic analysis; power grids; power system harmonics; sampling methods; signal detection; AC signal detection method; acquisition processing; data analysis; discrete Fourier transform; fence effect; fixed N synchronous sampling detection; grid aperiodic harmonic detection; harmonic analysis; periodic sine waveform; power grid; spectral leakage effect; variable N synchronous sampling method; aperiodic; discrete Fourier transform; frequency analysis; power grid harmonics; signal detection; synchronous sampling;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Future Power and Energy Engineering (ICFPEE), 2010 International Conference on
  • Conference_Location
    Shenzhen
  • Print_ISBN
    978-1-4244-7378-6
  • Electronic_ISBN
    978-1-4244-7379-3
  • Type

    conf

  • DOI
    10.1109/ICFPEE.2010.18
  • Filename