Switching surge test for air insulation design of 765 kV double circuit transmission line
Author :
Shim, J.W. ; Kim, J.B. ; Cho, S.B. ; Kwak, J.S.
Author_Institution :
Korea Electr. Power Res. Inst., Taejeon, South Korea
Volume :
2
fYear :
1997
fDate :
25 -30 May 1997
Firstpage :
1175
Abstract :
Test results of air insulation design of a Korea Electric Power Corporation 765 kV double circuit transmission line are presented. To determine the air clearance between 6-conductors and the tower body, upper crossarm and lower crossarm, respectively, suspension, tension and V insulator strings were tested in a full scale mockup by using a 4 MV outdoor impulse generator
Keywords :
air insulation; flashover; insulator testing; poles and towers; power system transients; power transmission lines; pulse generators; surges; 4 MV; 765 kV; Korea Electric Power Corporation; air clearance; air insulation design; double circuit transmission line; flashover voltage; full scale mockup; gap distance; insulator strings testing; lower crossarm; outdoor impulse generator; switching surge test; tower body; upper crossarm; Circuit testing; Conductors; Distributed parameter circuits; Flashover; Insulation testing; Poles and towers; Power transmission lines; Surges; Switching circuits; Voltage control;