Title :
Coordination of surge arresters with medium voltage current limiting fuses
Author_Institution :
AMEC Inc., Atlanta, GA, USA
Abstract :
Current limiting fuses are commonly used for unit substation primary protection. Simultaneously surge arresters are also provided on the primary side of the transformers, more so for the dry type transformers. The arc voltages generated by current limiting fuses will store energy in the inductive elements of a distribution system. This stored energy divides between the current limiting fuse and surge arrester and the surge arrester may operate. The paper outlines a procedure to calculate the energy diverted to the surge arresters, and shows that in some cases surge arresters may fail on operation of the current limiting fuses. Guidelines are developed for selection and application of the surge arresters at 13.8 kV, 4.16 kV and 2.4 kV voltage levels.
Keywords :
arresters; electric fuses; 13.8 kV; 2.4 kV; 4.16 kV; arc voltages; current limiting fuse; current limiting fuses; distribution system; dry type transformers; inductive elements; medium voltage current limiting fuses; surge arrester; surge arresters coordination; unit substation primary protection; Arresters; Circuit faults; Current limiters; Fault currents; Fuses; Medium voltage; Shape control; Size control; Surge protection; Transformers;
Conference_Titel :
Pulp and Paper Industry Technical Conference, 2001 Conference Record of.
Conference_Location :
Portland, OR, USA
Print_ISBN :
0-7803-6745-6
DOI :
10.1109/PAPCON.2001.952969