DocumentCode
3525198
Title
Field Trials of 400 kV Silicone Rubber Composite Insulators in a Coastal Location
Author
Robertson, J. ; Rowland, S.M. ; Xiong, Y. ; Hoffmann, S.
Author_Institution
Sch. of Electr. & Electron. Eng., Manchester Univ.
fYear
2006
fDate
15-18 Oct. 2006
Firstpage
365
Lastpage
368
Abstract
A number of silicone rubber composite insulators have been taken out of service after 15 years on a twin-circuit, 400 kV transmission line located in a coastal region in the south west of the UK. Visual observations and contact angle measurements are presented. The various surfaces of the insulators were degraded in a non-uniform manner, both in the rotational symmetry of the insulator and also along the length of the string. Leakage current and surface discharge measurements carried out in the laboratory are also presented. Deterioration of performance is identified, and this is found to vary along the length of the insulators.
Keywords
contact angle; leakage currents; power transmission lines; silicone rubber insulators; surface discharges; 15 year; 400 kV; coastal region; composite insulators; contact angle; leakage current; silicone rubber; surface discharge; transmission lines; Current measurement; Degradation; Goniometers; Insulation; Laboratories; Leakage current; Rubber; Sea measurements; Surface discharges; Transmission line measurements;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena, 2006 IEEE Conference on
Conference_Location
Kansas City, MO
Print_ISBN
1-4244-0546-7
Electronic_ISBN
1-4244-0547-5
Type
conf
DOI
10.1109/CEIDP.2006.311945
Filename
4105446
Link To Document