Title :
Determination of long-term performance of polymeric insulators for distribution lines by salt fog method
Author :
Homma, H. ; Takahashi, T. ; Kuroyagi, T. ; Miyauchi, Y. ; Matsuno, N. ; Saito, T. ; Mori, K. ; Matsuura, S. ; Fujii, K. ; Ohno, A. ; Ahagon, N.
Author_Institution :
Central Res. Inst. of Electr. Power Ind., Hokkaido Electr. Power Co., Hokaido
Abstract :
Polymeric transmission and distribution line insulators are gaining market share as a result of improved tolerance to pollution, ease of handling and installation. However, the surface of insulating materials, such as silicone rubber, is subject to long-term degradation during outdoor use. Determination of long-term performance of the polymeric insulators is important, and some artificial aging test methods have been approved. We carried out field exposure and artificial salt fog aging tests for a type of polymeric distribution line insulator. The long-term performance was evaluated by comparing the cumulative leakage charge during the field exposure test and the salt fog tests, which demonstrated that comparison of leakage current properties of the field exposure tests and that of laboratory aging tests provided a basis for life estimation of polymeric insulators exposed to salt pollution.
Keywords :
ageing; environmental degradation; leakage currents; polymer insulators; power distribution lines; silicone rubber insulators; transmission lines; artificial aging; distribution lines; environmental degradation; leakage current; long-term performance; polymeric insulators; salt fog method; silicone rubbers; Aging; Degradation; Insulator testing; Leakage current; Life testing; Plastic insulation; Pollution; Polymers; Rubber; Surface contamination;
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 2006 IEEE Conference on
Conference_Location :
Kansas City, MO
Print_ISBN :
1-4244-0546-7
Electronic_ISBN :
1-4244-0547-5
DOI :
10.1109/CEIDP.2006.311954