• DocumentCode
    3525423
  • Title

    Characterization of field-aged 400 kV silicone rubber composite insulators

  • Author

    Xiong, Y. ; Rowland, S.M. ; Robertson, J. ; Hoffmann, S.

  • Author_Institution
    Manchester Univ.
  • fYear
    2006
  • fDate
    15-18 Oct. 2006
  • Firstpage
    417
  • Lastpage
    420
  • Abstract
    A number of silicone rubber composite insulators have been removed after 15 years of service on a coastal 400 kV transmission line in the UK. Extensive analysis of their surface degradation is provided along with a description of their appearance. Material analysis shows cracking and oxidation of the surface. Ageing effects were far from uniform over each shed, the greatest oxidation being on the top surfaces of the sheds on the south side. Microscopy, EDX and FTIR were found to be the most useful and effective tools for analysis of these polymeric insulators.
  • Keywords
    ageing; composite insulators; cracks; fracture; oxidation; polymer insulators; silicone rubber; 400 kV; EDX; FTIR; ageing effects; polymeric insulators; silicone rubber composite insulators; surface cracking; surface degradation; surface oxidation; transmission line; Aging; Degradation; Insulation; Microscopy; Oxidation; Polymers; Rubber; Sea measurements; Surface cracks; Transmission lines;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 2006 IEEE Conference on
  • Conference_Location
    Kansas City, MO
  • Print_ISBN
    1-4244-0547-5
  • Electronic_ISBN
    1-4244-0547-5
  • Type

    conf

  • DOI
    10.1109/CEIDP.2006.311958
  • Filename
    4105459