Using a high-speed camera, the fundamental behaviors of arcs on the surfaces of two types of 300 kN porcelain insulators were studied under DC voltages. The test results showed that it was quite easy for the arcs on porcelain insulator surfaces to levitate from insulator surfaces in high altitude areas (1970 m). The influence of angles, used for different V-strings of insulator configurations, on DC flashover behaviors of contaminated insulators was very obvious. In this paper, the effects of the angles of V-strings on DC flashover characteristics of two types of polluted insulators (anti-fog insulator and tri-shed DC suspension insulator) were investigated.
Keywords
arcs (electric); flashover; insulator contamination; porcelain insulators; power transmission lines; 1970 m; DC flashover characteristics; DC voltages; V-strings insulator configurations; antifog insulator; arcs; contaminated insulators; high-speed camera; insulator surfaces; polluted insulators; porcelain insulators; trished DC suspension insulator; Cable insulation; Dielectrics and electrical insulation; Flashover; Insulator testing; Pollution; Porcelain; Power transmission lines; Structural beams; Surface contamination; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena, 2006 IEEE Conference on
Conference_Location
Kansas City, MO
Print_ISBN
1-4244-0547-5
Electronic_ISBN
1-4244-0547-5
Type
conf
DOI
10.1109/CEIDP.2006.311966
Filename
4105467
Link To Document