• DocumentCode
    3525803
  • Title

    Effect of ageing on the impulse breakdown strength of oil-impregnated pressboard used in power transformers

  • Author

    Ding, H.-Z. ; Wang, Z.D. ; Jarman, P.N.

  • Author_Institution
    Sch. of Electr. Eng. & Electron., Manchester Univ.
  • fYear
    2006
  • fDate
    15-18 Oct. 2006
  • Firstpage
    497
  • Lastpage
    500
  • Abstract
    This paper presents the lightning impulse voltage test results of service-aged pressboards taken from a failed power transformer after 29 years´ service. Impulse voltage tests have revealed that there is a significant reduction of breakdown voltages, most probably due to the degradation of mechanical strength. The minimum impulse electric strength may reduce approximately by 30% after 29 years´ service. Test results on the service-aged pressboard also indicate that when the moisture content in pressboard is less than 4%, there is no significant correlation between the reductions of the impulse electric strength with increasing moisture content.
  • Keywords
    ageing; electric breakdown; power transformer insulation; ageing effect; breakdown voltages; impulse breakdown strength; impulse electric strength; lightning impulse voltage; mechanical strength degradation; moisture content; oil-impregnated pressboard; power transformers; Aging; Dielectric breakdown; Dielectrics and electrical insulation; Electric breakdown; Electrodes; Moisture; Oil insulation; Petroleum; Power transformer insulation; Power transformers;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 2006 IEEE Conference on
  • Conference_Location
    Kansas City, MO
  • Print_ISBN
    1-4244-0547-5
  • Electronic_ISBN
    1-4244-0547-5
  • Type

    conf

  • DOI
    10.1109/CEIDP.2006.311978
  • Filename
    4105479