Title :
Computation of lightning induced overvoltage on overhead power line
Author :
Kannu, P. Durai ; M, Joy Thomas
Author_Institution :
Dept. of High Voltage Eng., Indian Inst. of Sci., Bangalore, India
Abstract :
This paper presents the results of the lightning induced voltage computation on various conductors of a 33 kV, 3φ overhead power line with different conductor arrangements. It has been seen that the induced voltage is more on the conductors in the case of a vertical configuration as compared to a horizontal configuration for single circuit arrangement. Voltages induced on the conductors closer to the strike point are more and depend on the conductor height from ground. Computations also show that presence of ground wire reduces the induced voltage on phase conductors
Keywords :
power overhead lines; 3 phase overhead power line; 33 kV; conductor arrangements; conductor height; conductors; ground wire; horizontal configuration; induced voltage; induced voltages; lightning induced overvoltage; overhead power line; single circuit arrangement; vertical configuration;
Conference_Titel :
High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
Conference_Location :
London
Print_ISBN :
0-85296-719-5
DOI :
10.1049/cp:19990570