• DocumentCode
    3527276
  • Title

    VFTO computation in 420 kV GIS

  • Author

    Kumar, V. Vinod ; M, Joy Thomas ; Naidu, M.S.

  • Author_Institution
    Dept. of High Voltage Eng., Indian Inst. of Sci., Bangalore, India
  • Volume
    1
  • fYear
    1999
  • fDate
    1999
  • Firstpage
    319
  • Abstract
    This paper presents the results of very fast transient overvoltage (VFTO) computations that have been carried out using EMTP for various switching conditions in a 420 kV gas insulated substation (GIS). The variation of VFTO peak along the nodes for disconnector and circuit breaker operations as well as the variation of VFTO with different trapped charges have been studied. The results indicate a distinct pattern of variation of VFTO peak along the nodes of the GIS in the case of disconnector switch operation as compared to that of circuit breaker operation. It has also been noticed that the variation of VFTO peak levels are not proportional to the increase in the trapped charge
  • Keywords
    gas insulated substations; 420 kV; EMTP; GIS; VFTO computation; circuit breaker operation; disconnector operation; gas insulated substation; switching conditions; trapped charges; very fast transient overvoltage;