• DocumentCode
    3529446
  • Title

    Line protection: Redundancy, reliability, and affordability

  • Author

    Schweitzer, E.O. ; Whitehead, D. ; Ferrer, H.J.A. ; Tziouvaras, D.A. ; Costello, D.A. ; Escobedo, D.S.

  • fYear
    2011
  • fDate
    11-14 April 2011
  • Firstpage
    1
  • Lastpage
    24
  • Abstract
    In this paper, we apply fault tree analysis to compare the dependability and security of line protection schemes with different degrees of redundancy. We also compare the scheme costs. For each scheme, we use a basic protection scheme as the reference. We then evaluate schemes with double redundancy and two-out-of-three voting schemes. We also evaluate the effect of comprehensive commissioning testing, hidden failures, and common-mode failures, as well as using relays from the same or different manufacturers in redundant schemes.
  • Keywords
    failure analysis; power system security; power transmission economics; power transmission faults; power transmission lines; power transmission protection; power transmission reliability; relays; common-mode failure; comprehensive commissioning testing; double redundancy; fault tree analysis; line protection security; relay; transmission line protection security scheme; two-out-of-three voting scheme; Maintenance engineering; Power system reliability; Redundancy; Relays; Testing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Protective Relay Engineers, 2011 64th Annual Conference for
  • Conference_Location
    College Station, TX
  • Print_ISBN
    978-1-4577-0494-9
  • Type

    conf

  • DOI
    10.1109/CPRE.2011.6035495
  • Filename
    6035495