DocumentCode :
3531181
Title :
Distribution feeder fault location using IED and FCI information
Author :
Gong, Yanfeng ; Guzmán, Armando
fYear :
2011
fDate :
11-14 April 2011
Firstpage :
168
Lastpage :
177
Abstract :
Fault location in distribution feeders is a difficult task. Traditional impedance-based fault location methods assume that all feeder sections have the same impedance characteristics. This assumption introduces errors on feeders having sections with different conductor types and different tower configurations. This paper describes a new impedance-based method that uses the impedances and length of each feeder section and relay event reports to calculate possible fault locations. The method is complemented with faulted circuit indicators with communications abilities to reduce the number of possible fault locations. The paper compares calculation results obtained with the traditional and new methods using field cases and shows the benefit of using the new method.
Keywords :
fault location; power distribution faults; power distribution lines; FCI information; IED information; conductor; distribution feeder fault location; faulted circuit indicators; impedance characteristics; impedance-based fault location methods; tower configurations; Circuit faults; Digital relays; Fault location; Radio frequency; Resistance; Voltage measurement;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Protective Relay Engineers, 2011 64th Annual Conference for
Conference_Location :
College Station, TX
Print_ISBN :
978-1-4577-0494-9
Type :
conf
DOI :
10.1109/CPRE.2011.6035617
Filename :
6035617
Link To Document :
بازگشت