• DocumentCode
    3537510
  • Title

    New method for comparison of chopped waveforms in impulse transformer tests

  • Author

    Slomovitz, D. ; Slomovitz, G. ; Joskowicz, J.

  • Author_Institution
    Itel Electron., Montevideo, Uruguay
  • fYear
    2012
  • fDate
    3-5 Sept. 2012
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    Power transformers must be evaluated under impulse tests. For that, it is necessary to compare voltage and current waveforms corresponding to reduced-level and full-level voltages. Any difference may correspond to a failure in the transformer under test. This test is based on the principle that there is no change in the generation of the impulse voltage. However, with chopped waveforms, many impulse generators have significant differences in the time of chopping that make difficult to get a conclusion on the test result. This paper presents a new algorithm that generates reduced-level chopped voltage and current waveforms, with arbitrary chopping time, from a couple of reduced voltage of full and chopped waveforms. In this way, it is possible to compare full-level voltage chopped waveforms with reduced-level ones with different chopping times.
  • Keywords
    impulse testing; power transformers; arbitrary chopping time; chopped waveform; current waveform; full-level voltage; impulse power transformer test; reduced-level voltage; voltage waveform; Dispersion; Educational institutions; Generators; IEC standards; Laboratories; Power transformers; Impulse test; arc; chopped waveform; comparison; dielectric; high voltage; multiple chopping gap; rod-rod gap; sphere gap; standard; transfer function; transformer;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution: Latin America Conference and Exposition (T&D-LA), 2012 Sixth IEEE/PES
  • Conference_Location
    Montevideo
  • Print_ISBN
    978-1-4673-2672-8
  • Type

    conf

  • DOI
    10.1109/TDC-LA.2012.6319136
  • Filename
    6319136