    Factor for dielectric strength reduction due to fibrous contaminants in XLPE

  • Author

    Iinuma, K. ; Miyata, Hiroyuki ; Takahashi, Tohru ; Yamamoto, Shuji

  • Author_Institution
    Fujikura Ltd., Japan
  • fYear
    1995
  • fDate
    17-20 Sep 1995
  • Firstpage
    105
  • Lastpage
    108
  • Abstract
    We investigate the effect on breakdown strength reduction by employing several kinds of fiber, in which each effect is classified in prebreakdown by partial discharge detection and electroluminescence measurement. In the same size fiber, breakdown strength decreases in the order: solid synthetic fiber>cotton fiber>hollow synthetic fiber>copper fiber. The partial discharge behavior is clearly different between hollow fiber and copper fiber. The electrical tree characteristics are also discussed
  • Keywords
    XLPE insulation; electric breakdown; electric strength; electroluminescence; fibre reinforced composites; impurities; insulation testing; partial discharges; trees (electrical); XLPE; breakdown strength reduction; copper fiber; cotton fiber; dielectric strength reduction; electrical tree characteristics; electroluminescence; fibrous contaminants; hollow synthetic fiber; partial discharge detection; prebreakdown; solid synthetic fiber; Copper; Cotton; Dielectric breakdown; Electric breakdown; Electroluminescence; Optical fiber testing; Partial discharge measurement; Partial discharges; Shape measurement; Solids;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulating Materials, 1995. International Symposium on
  • Conference_Location
    Tokyo
  • Print_ISBN
    4-88686-047-8
  • Type

    conf

  • DOI
    10.1109/ISEIM.1995.496519
  • Filename
    496519