• DocumentCode
    3537840
  • Title

    Some aspects of water tree growth in XLPE insulation exposed to DC voltage

  • Author

    Czaszejko, Tadeusz

  • Author_Institution
    Dept. of Electr. & Comput. Syst. Eng., Monash Univ., Melbourne, Vic., Australia
  • fYear
    1995
  • fDate
    17-20 Sep 1995
  • Firstpage
    145
  • Lastpage
    148
  • Abstract
    A preliminary study of the influence of the short exposure to DC voltage on the growth of water trees in XLPE cable insulation was performed. The DC voltage of 4U0 (where U0 is the rms rated voltage) was applied for the duration of 15 minutes prior to AC aging, in one set of samples, and in the middle of AC aging, in another set of identical samples. The results have shown an increase of the average length of water trees grown in samples subjected to DC voltage compared with those not exposed to DC voltage. The result was similar for accelerated aging with the liquid needle electrode method and for plain samples aged under rated voltage
  • Keywords
    XLPE insulation; ageing; insulation testing; life testing; power cable insulation; trees (electrical); 15 min; DC voltage; XLPE insulation; accelerated aging; liquid needle electrode method; power cable insulation; rated voltage; rms rated voltage; water tree growth; Aging; Cable insulation; Cable shielding; Cables; Dielectrics and electrical insulation; Electrodes; Needles; Polyethylene; Trees - insulation; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulating Materials, 1995. International Symposium on
  • Conference_Location
    Tokyo
  • Print_ISBN
    4-88686-047-8
  • Type

    conf

  • DOI
    10.1109/ISEIM.1995.496529
  • Filename
    496529