• DocumentCode
    3558441
  • Title

    Voltage waveform distortion in synchronous generators with rectifier loading

  • Author

    Bonwick, W.J.

  • Author_Institution
    Monash University, Melbourne, Australia
  • Volume
    127
  • Issue
    1
  • fYear
    1980
  • fDate
    1/1/1980 12:00:00 AM
  • Firstpage
    13
  • Lastpage
    19
  • Abstract
    Armature voltage waveforms of synchronous generators with bridge rectifier loads are distorted to a degree determined by the generator transient (or subtransient) inductances. A generator with zero transient saliency (z.t.s.) has a true sinusoidal waveform, apart from commutation disturbances occurring four times a cycle. The disturbance level is reduced by decreasing the generator transient inductance. Reduced waveform distortion becomes important when the generator is loaded with parallel d.c./a.c. loads and when the a.c. load is sensitive to waveform harmonics. A z.t.s. generator is recommended for such mixed-load applications. The operating equations for the z.t.s. generator have been simplified from previous work and performance predictions are readily made. To some extent, the behaviour of a z.t.s. generator with a rectifier load closely resembles simple constant-source-inductance rectifier operation. Some experimental results are given for a cylindrical-rotor z.t.s. generator and for a salient pole generator with two different damper winding arrangements.
  • Keywords
    electric distortion; harmonics; inductance; load (electric); synchronous generators; transients; bridge rectifier loads; cylindrical rotor; harmonics; salient pole; synchronous generators; transient inductance; voltage waveforms; waveform distortion;
  • fLanguage
    English
  • Journal_Title
    Electric Power Applications, IEE Proceedings B
  • Publisher
    iet
  • Conference_Location
    1/1/1980 12:00:00 AM
  • ISSN
    0143-7038
  • Type

    jour

  • DOI
    10.1049/ip-b:19800003
  • Filename
    4643178