• DocumentCode
    3558727
  • Title

    A dynamic on-line parameter identification and full-scale system experimental verification for large synchronous machines

  • Author

    Zhao, Zhengming ; Zheng, Fungshi ; Gao, Jide ; Xu, Longya

  • Author_Institution
    Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
  • Volume
    10
  • Issue
    3
  • fYear
    1995
  • fDate
    9/1/1995 12:00:00 AM
  • Firstpage
    392
  • Lastpage
    398
  • Abstract
    An on-line parameter identification and full-scale experimental verification for large synchronous machines (>50 MVA) is presented in this paper. A step change of excitation is imposed to a generator when the machine is in normal operation. The transient voltages, currents and the power angle are recorded. Based on the large disturbance equations and using the measured power angle as an observation argument in an identification algorithm, the synchronous machine electrical parameters (xd, xd\´, xd", Tdo\´, Tdo", xq, xq", Tqo") and mechanical parameters (H,D) are obtained. In addition, the system parameters (equivalent infinite bus voltage Vbus and line reactance xe) are identified as well. The proposed method has been repetitively applied to turbogenerators and hydrogenerators with capacities up to 300 MVA. In particular, a field test has been conducted on a system with a capacity of 15000 MVA. The experimental results from all of the full-scale tests are consistent and the effectiveness of the proposed on-line identification method is verified. The plant experiences indicate that by adopting the identified parameters, the stability margin of the generator can be improved by up to 5%, resulting in 30-50 MVA more power generation
  • Keywords
    hydroelectric generators; machine theory; parameter estimation; stability; turbogenerators; dynamic on-line parameter identification; electrical parameters; equivalent infinite bus voltage; excitation step change; hydrogenerators; large disturbance equations; line reactance; mechanical parameters; power angle measurement; stability margin; synchronous machines; transient currents; transient voltages; turbogenerators; Electric variables measurement; Equations; Goniometers; Mechanical variables measurement; Parameter estimation; Power generation; Power measurement; Q measurement; Synchronous machines; Voltage;
  • fLanguage
    English
  • Journal_Title
    Energy Conversion, IEEE Transactions on
  • Publisher
    ieee
  • Conference_Location
    9/1/1995 12:00:00 AM
  • ISSN
    0885-8969
  • Type

    jour

  • DOI
    10.1109/60.464859
  • Filename
    464859