DocumentCode :
3559174
Title :
Influence of voltage application history on insulation test with one-minute step-up method
Author :
Tsuboi, Toshihiro ; Takami, Jun ; Okabe, Shigemitsu
Author_Institution :
R&D Center, Tokyo Electr. Power Co., Yokohama
Volume :
15
Issue :
5
fYear :
2008
fDate :
10/1/2008 12:00:00 AM
Firstpage :
1261
Lastpage :
1270
Abstract :
For the development of test conditions for a short-duration power-frequency withstand voltage test, which is one of the insulation specifications of substation equipment, there is a precise method of evaluating reliability using a Weibull distribution function. For this method, "independence method" and "accumulation method" have been proposed in order to handle the coexistence of multiple voltage levels. In this paper, an insulation test based on the one-minute step-up method as condition for the coexistence of multiple voltage levels is used to calculate and evaluate the test results using these two methods. Consequently, the insulation characteristics obtained from the one-minute step-up test are found to have differences from the true values. If the independence method is adopted, there is a certain deviation regardless of the Weibull time shape parameter "a-value" and, the smaller the Weibull voltage shape parameter "m-value", the larger the deviation. If the accumulation method is adopted, on the other hand, the larger the "a-value" or the smaller the "m-value", the larger the deviation. The 50% breakdown voltage value, the standard deviation "sigma-value", and the "m-value" that can be obtained from the insulation test based on the one-minute step-up method were evaluated for their deviations from the true values. The results suggest that, when a test is conducted on an oil-filled transformer, the design may turn out to be on the dangerous side due to overestimation of the dielectric strength by around 8%.
Keywords :
Weibull distribution; electric breakdown; electric strength; insulation testing; substation insulation; Weibull distribution function; accumulation method; breakdown voltage; dielectric strength; independence method; insulation testing; oil-filled transformer; one-minute step-up method; short-duration power-frequency withstand voltage test; standard deviation; substation equipment reliability; Dielectric breakdown; Dielectrics and electrical insulation; History; Insulation testing; Oil insulation; Power transformer insulation; Shape; Substations; Voltage; Weibull distribution; Power-frequency withstand voltage test; Weibull distributions; breakdown voltage-time characteristics; one minute step-up method; reliability evaluation;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
Conference_Location :
10/1/2008 12:00:00 AM
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/TDEI.2008.4656233
Filename :
4656233