DocumentCode :
3559486
Title :
Characterization of Clamp-On Current Transformers Under Nonsinusoidal Conditions
Author :
Cataliotti, Antonio ; Cara, Dario Di ; Emanuel, Alexander E. ; Nuccio, Salvatore
Author_Institution :
Elettron. e delle Telecomun. (DIEET), Univ. di Palermo, Palermo
Volume :
24
Issue :
1
fYear :
2009
Firstpage :
373
Lastpage :
380
Abstract :
This paper reports the performance of clamp-on current transformers under nonsinusoidal conditions. A set of experimental measurements helped to determine the ratio and the phase errors under two conditions: 1) sinusoidal excitation with frequencies from 45 to 1000 Hz and 2) nonsinusoidal excitation using the fundamental frequency and one harmonic, with adjusted phase shift. It was found that ratio and phase errors are affected by the phase angle between the harmonic and the fundamental and the harmonic amplitude. The effects of conductor location in the current transformer´s window and of the air-gap width were also investigated. It was concluded that harmonic phase and ratio errors measured in nonsinusoidal conditions can be higher than the ones determined by the frequency response.
Keywords :
current transformers; electric current measurement; power system harmonics; air-gap width; clamp-on current transformer; conductor location effect; frequency 45 Hz to 1000 Hz; harmonic current measurement; harmonic phase error measurement; nonsinusoidal conditions; power system harmonics; sinusoidal excitation; Clamp-on current transformers; current transformers (CTs); frequency response; power system harmonics; transducers;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
Conference_Location :
12/12/2008 12:00:00 AM
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2008.2005707
Filename :
4711064
Link To Document :
بازگشت