DocumentCode :
3559813
Title :
PD pulse burst behavior of a transformer type synthetic organic ester fluid
Author :
Pompili, M. ; Mazzetti, C. ; Bartnikas, R.
Author_Institution :
Electr. Eng. Dept., Univ. of Roma, Rome
Volume :
15
Issue :
6
fYear :
2008
fDate :
12/1/2008 12:00:00 AM
Firstpage :
1498
Lastpage :
1506
Abstract :
The partial discharge (PD) pulse burst characteristics of a transformer type synthetic organic ester fluid were compared with those of an equivalent transformer type mineral oil. Wide and narrow bandwidth measurements were carried out to determine simultaneously the apparent charge transfers associated with the overall PD pulse burst as well as that of the individual discrete pulses within the PD pulse burst. The PD pulse burst behavior was found to be similar in both insulating liquids. The discharge cavity formation times ranged from 0.5 to 1.5 mus, while the charge transfers associated with the PD pulse bursts in the liquids were found to extend from approximately 5 to 30 pC.
Keywords :
partial discharges; transformer oil; apparent charge transfers; discharge cavity formation; insulating liquids; partial discharge pulse burst characteristics; transformer type mineral oil; transformer type synthetic organic ester fluid; Bandwidth; Charge transfer; Current measurement; Minerals; Oil insulation; Partial discharges; Petroleum; Power transformer insulation; Pulse measurements; Pulse transformers; Partial discharges, mineral oil, synthetic ester;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
Conference_Location :
12/1/2008 12:00:00 AM
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/TDEI.2008.4712651
Filename :
4712651
Link To Document :
بازگشت