• DocumentCode
    3561345
  • Title

    An Unsynchronized Measurements Correction Method for Two-Terminal Fault-Location Problems

  • Author

    Yu, Chi-Shan

  • Author_Institution
    Dept. of Electr. Eng., Nat. Taipei Univ. of Technol., Taipei, Taiwan
  • Volume
    25
  • Issue
    3
  • fYear
    2010
  • fDate
    7/1/2010 12:00:00 AM
  • Firstpage
    1325
  • Lastpage
    1333
  • Abstract
    This paper presents a method to correct the unsynchronized measurements for two-terminal fault-location problems. First, a synchronization index is defined to check whether the measurements are synchronized. A modified secant method-based algorithm is then developed to obtain a synchronization angle and correct the unsynchronized measurements. When the unsynchronized measurements are corrected, the fault location can be simultaneously obtained from the intermediate result of the proposed computation. Thus, although the proposed method is developed to correct the unsynchronized measurements, the fault-location problem can also be solved. Compared with the previous works, the proposed iteration equation is simpler. The MATLAB/SIMULINK simulator is used to evaluate the effectiveness of the proposed method.
  • Keywords
    fault location; power cables; power system protection; synchronisation; iteration equation; line protection systems; modified secant method-based algorithm; synchronization index; two-terminal fault-location problems; unsynchronized measurements correction method; Circuit faults; Convergence; Equations; Fault location; Impedance; Phasor measurement units; Position measurement; Protection; Protective relaying; Time measurement; Fault location; synchronization angle; synchronization index; unsynchronized measurements;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • Conference_Location
    7/1/2010 12:00:00 AM
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2009.2037631
  • Filename
    5491352