DocumentCode
3561345
Title
An Unsynchronized Measurements Correction Method for Two-Terminal Fault-Location Problems
Author
Yu, Chi-Shan
Author_Institution
Dept. of Electr. Eng., Nat. Taipei Univ. of Technol., Taipei, Taiwan
Volume
25
Issue
3
fYear
2010
fDate
7/1/2010 12:00:00 AM
Firstpage
1325
Lastpage
1333
Abstract
This paper presents a method to correct the unsynchronized measurements for two-terminal fault-location problems. First, a synchronization index is defined to check whether the measurements are synchronized. A modified secant method-based algorithm is then developed to obtain a synchronization angle and correct the unsynchronized measurements. When the unsynchronized measurements are corrected, the fault location can be simultaneously obtained from the intermediate result of the proposed computation. Thus, although the proposed method is developed to correct the unsynchronized measurements, the fault-location problem can also be solved. Compared with the previous works, the proposed iteration equation is simpler. The MATLAB/SIMULINK simulator is used to evaluate the effectiveness of the proposed method.
Keywords
fault location; power cables; power system protection; synchronisation; iteration equation; line protection systems; modified secant method-based algorithm; synchronization index; two-terminal fault-location problems; unsynchronized measurements correction method; Circuit faults; Convergence; Equations; Fault location; Impedance; Phasor measurement units; Position measurement; Protection; Protective relaying; Time measurement; Fault location; synchronization angle; synchronization index; unsynchronized measurements;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
Conference_Location
7/1/2010 12:00:00 AM
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2009.2037631
Filename
5491352
Link To Document