• DocumentCode
    356170
  • Title

    Sub-cycle detection of incipient cable splice faults to prevent cable damage

  • Author

    Kojovic, Ljubomir A. ; Williams, Charles W., Jr.

  • Author_Institution
    Cooper Power Syst., Franksville, WI, USA
  • Volume
    2
  • fYear
    2000
  • fDate
    2000
  • Firstpage
    1175
  • Abstract
    This paper presents an innovative method for subcycle detection of incipient cable failures caused by self-clearing faults occurring in cable splices due to insulation breakdown. Because of their short duration, conventional overcurrent protection will not detect these types of faults. The protection scheme described in this paper has been integrated into a universal relay platform. It is fast enough to operate for sub-cycle faults and has the logic to differentiate them from other types of faults. Imminent cable failure can be detected
  • Keywords
    cable jointing; electric breakdown; fault location; power cable insulation; power cable testing; power distribution faults; relay protection; cable damage prevention; cable protection; distribution systems; imminent cable failure detection; incipient cable splice faults detection; insulation breakdown; overcurrent protection; relay protection; self-clearing faults; short duration; sub-cycle detection; sub-cycle faults; universal relay platform; Cable insulation; Circuit faults; Electric breakdown; Electrical fault detection; Fault detection; Power cable insulation; Power cables; Protection; Protective relaying; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Society Summer Meeting, 2000. IEEE
  • Conference_Location
    Seattle, WA
  • Print_ISBN
    0-7803-6420-1
  • Type

    conf

  • DOI
    10.1109/PESS.2000.867545
  • Filename
    867545