Title :
A new distribution automation technique without the need for communication link
Author :
Chen, Fei ; Dong, Inzhou ; Bo, Z. ; Caunce, B.R.J.
Author_Institution :
Tsinghua Univ., Beijing, China
Volume :
2
fYear :
2004
Firstpage :
689
Abstract :
The paper presents a new technique for distribution automation based on an accelerated protection theory. A specially designed directional under voltage relay is arranged to trip for faults on the line section from the source direction of the system. The relays on the source side of the line section detect the system balanced operation condition and accelerated operation isolates the fault from both ends of the line section. Extensive simulation studies with respect to a typical open ring main system show that the proposed technique is able to remove a faulted line section quickly and accurately from both ends and, therefore, enables the power supply to be quickly restored to the healthy line sections.
Keywords :
overcurrent protection; power distribution control; power distribution protection; power transmission protection; relay protection; accelerated overcurrent protection; accelerated protection theory; directional under voltage relay; distribution automation technique; faulted line section; open ring main system; transmission line control; transmission line protection; Acceleration; Automatic control; Automation; Circuit faults; Communication system control; Fault detection; Microprocessors; Power system protection; Protective relaying; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Universities Power Engineering Conference, 2004. UPEC 2004. 39th International
Print_ISBN :
1-86043-365-0
Type :
conf
Filename :
1492108
Link To Document :
بازگشت