DocumentCode :
356221
Title :
Study of partial discharge localization methods for EHV prefabricated joint
Author :
Chen Min ; Urano, Koji ; Kato, Akira ; Sakaguchi, Yasuo ; Okamoto, Gaku ; Ueno, Hiroto ; Hirotu, Kenichi ; Jinno, A. ; Okada, Masahiko ; Yoshikawa, Nobuaki
Author_Institution :
Sumitomo Electr. Ind. Ltd., Osaka, Japan
Volume :
1
fYear :
2000
fDate :
2000
Firstpage :
475
Abstract :
With an example of PD localization for EHV cable joint on site, multiple method of PD localization is studied in this paper, including (1) method of using metallic foil electrode sensors, (2) method of excitation by X-ray radiation and a foil electrode sensor, and (3) method of applying acoustic emission sensors and a foil electrode sensor. Compared with the conventional method of PD localization for long distance cables of more than hundreds of meters, it is more difficult to localize a PD for a pre-fabricated type of joint of only a short length of around 2 m, due to problems in measurement such as the disturbance of pulse reflection, the complicated route of pulse propagation and the difference of pulse propagation velocity. The results of the example also show that this multiple method can give a high accuracy of PD localization
Keywords :
X-ray applications; acoustic emission testing; cable jointing; electrodes; foils; partial discharge measurement; power cables; EHV cable joint; EHV prefabricated joint; X-ray radiation excitation; acoustic emission sensors; metallic foil electrode sensors; partial discharge localization methods; pulse propagation; pulse propagation velocity; pulse reflection; Acoustic sensors; Cable insulation; Cable shielding; Electrodes; Partial discharges; Position measurement; Power cables; Pulse measurements; Time measurement; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering Society Summer Meeting, 2000. IEEE
Conference_Location :
Seattle, WA
Print_ISBN :
0-7803-6420-1
Type :
conf
DOI :
10.1109/PESS.2000.867632
Filename :
867632
Link To Document :
بازگشت