DocumentCode
356221
Title
Study of partial discharge localization methods for EHV prefabricated joint
Author
Chen Min ; Urano, Koji ; Kato, Akira ; Sakaguchi, Yasuo ; Okamoto, Gaku ; Ueno, Hiroto ; Hirotu, Kenichi ; Jinno, A. ; Okada, Masahiko ; Yoshikawa, Nobuaki
Author_Institution
Sumitomo Electr. Ind. Ltd., Osaka, Japan
Volume
1
fYear
2000
fDate
2000
Firstpage
475
Abstract
With an example of PD localization for EHV cable joint on site, multiple method of PD localization is studied in this paper, including (1) method of using metallic foil electrode sensors, (2) method of excitation by X-ray radiation and a foil electrode sensor, and (3) method of applying acoustic emission sensors and a foil electrode sensor. Compared with the conventional method of PD localization for long distance cables of more than hundreds of meters, it is more difficult to localize a PD for a pre-fabricated type of joint of only a short length of around 2 m, due to problems in measurement such as the disturbance of pulse reflection, the complicated route of pulse propagation and the difference of pulse propagation velocity. The results of the example also show that this multiple method can give a high accuracy of PD localization
Keywords
X-ray applications; acoustic emission testing; cable jointing; electrodes; foils; partial discharge measurement; power cables; EHV cable joint; EHV prefabricated joint; X-ray radiation excitation; acoustic emission sensors; metallic foil electrode sensors; partial discharge localization methods; pulse propagation; pulse propagation velocity; pulse reflection; Acoustic sensors; Cable insulation; Cable shielding; Electrodes; Partial discharges; Position measurement; Power cables; Pulse measurements; Time measurement; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Society Summer Meeting, 2000. IEEE
Conference_Location
Seattle, WA
Print_ISBN
0-7803-6420-1
Type
conf
DOI
10.1109/PESS.2000.867632
Filename
867632
Link To Document