• DocumentCode
    3574228
  • Title

    Comparison of pollution flashover performance of various insulators

  • Author

    Sivaraman, M. ; Sivadasan, J.

  • Author_Institution
    Dept. of EEE, Nat. Eng. Coll., Kovilpatti, India
  • fYear
    2014
  • Firstpage
    148
  • Lastpage
    152
  • Abstract
    In this paper, there are two different artificial pollution such as coastal and desert were applied on three different types of insulators namely, porcelain anti-fog disc type, disc type glass insulator and composite long rod type insulator. As per the standard IEC 61245 the pollution test were performed in the artificial climate chamber by solid layer pollution method under HVDC supply. By using even rising method, the average flashover voltage can be calculated. Based on flashover voltage and insulating material profiles, the flashover gradients of three insulators were determined. Comparing the test results, porcelain having better with stand capability on both region tests due to higher leakage distance than others.
  • Keywords
    HVDC power transmission; composite insulators; flashover; insulator contamination; insulator testing; porcelain insulators; HVDC supply; IEC 61245 standard; artificial climate chamber; artificial pollution; average flashover voltage; composite long rod type insulator; disc type glass insulator; even rising method; flashover gradients; insulating material profiles; leakage distance; pollution flashover performance; pollution test; porcelain anti-fog disc type insulator; solid layer pollution method; Flashover; Glass; HVDC transmission; Insulators; Pollution; Porcelain; Sea measurements; flashover; insulator; pollution; withstand;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Circuit, Power and Computing Technologies (ICCPCT), 2014 International Conference on
  • Print_ISBN
    978-1-4799-2395-3
  • Type

    conf

  • DOI
    10.1109/ICCPCT.2014.7054774
  • Filename
    7054774