DocumentCode :
357936
Title :
Experience with UHF PD detection in GIS substations
Author :
Schichler, Uwe ; Gorablenkow, Jörg
Author_Institution :
Power Transmission & Distribution High Voltage Div., Siemens AG, Berlin, Germany
Volume :
1
fYear :
2000
fDate :
2000
Firstpage :
286
Abstract :
This paper handles the experience with the ultra high frequency (UHF) partial discharge (PD) detection for GIS. After a short description of a typical PD monitoring system the Cigre sensitivity verification for the UHF method is explained. Examples of PD events from on-site testing and service monitoring are given and discussed in terms of risk assessment. A new procedure for risk assessment of moving particles by detection of PD bursts is introduced
Keywords :
UHF measurement; gas insulated substations; insulation testing; partial discharge measurement; Cigre sensitivity; GIS substation; UHF partial discharge detection; moving particles; on-site testing; risk assessment; service monitoring; Computational Intelligence Society; Frequency; Geographic Information Systems; Monitoring; Partial discharges; Risk management; Substations; Testing; UHF measurements; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Properties and Applications of Dielectric Materials, 2000. Proceedings of the 6th International Conference on
Conference_Location :
Xi´an
Print_ISBN :
0-7803-5459-1
Type :
conf
DOI :
10.1109/ICPADM.2000.875687
Filename :
875687
Link To Document :
بازگشت