Title :
Discharge current method-a test procedure for plastic-insulated medium-voltage cables
Author :
Muhr, Michael ; Woschitz, Rudolf
Author_Institution :
Inst. fur Hochspannungstech. mit Versuchsanstalt, Tech. Univ. Graz, Austria
Volume :
1
fYear :
2000
fDate :
2000
Firstpage :
435
Abstract :
The diagnostic method for medium voltage cables based on the method of discharge current is an integral measurement technique, which means that the dielectric properties of an insulating material can only be measured in general, singular vacancies cannot be detected. The non-linear correlation between charging voltage and discharge current is a criterion for the state of ageing of the insulating material and gives information about its condition
Keywords :
ageing; dielectric measurement; discharges (electric); insulation testing; plastics; power cable insulation; power cable testing; ageing; diagnostic method; dielectric properties; discharge current; integral measurement technique; medium voltage cable; plastic insulation testing; Aging; Cable insulation; Circuit testing; Current measurement; Dielectric materials; Dielectric measurements; Dielectrics and electrical insulation; Materials testing; Medium voltage; Plastic insulation;
fLanguage :
English