DocumentCode :
3580994
Title :
Analysis of substation noise prediction based on equivalent source method
Author :
Hu Jingzhu ; Liu Dichen ; Liao Qingfen ; Han Xiangyu ; Yan Yang
Author_Institution :
Dept. Of Electr. Eng., Wuhan Univ., Wuhan, China
fYear :
2014
Firstpage :
1
Lastpage :
5
Abstract :
When predicting the noise level of substation, the model of transformers and reactors as noise sources is very important. A new acoustic mode of the transformers and reactors is built in ultra-high voltage substation. Each of the transformers and reactors is equivalent to several point sources based on equivalent source method. And in the process of the equivalent, the measurement and calculation are made easier by using sound power level to represent the equivalent sources intensity. A model of 9 equivalent point sources is chosen to verify the accuracy of the model. This acoustic model of the transformers and reactors is combined with outdoor point sound sources attenuation theory to predict the substation noise value. Simulation of a 1000kV substation has been down which shows that the model is feasible to calculate the noise level anywhere inside the substation.
Keywords :
noise (working environment); substations; acoustic model; equivalent source method; equivalent sources intensity; noise sources; reactors; sound power level; substation noise level; substation noise value prediciton; transformers; ultra-high voltage substation; voltage 1000 kV; Attenuation; Inductors; Noise; Noise level; Predictive models; Substations; acoustic model; equivalent source approach; noise prediction; planar source; point source; substation;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Energy Engineering Conference (APPEEC), 2014 IEEE PES Asia-Pacific
Type :
conf
DOI :
10.1109/APPEEC.2014.7066010
Filename :
7066010
Link To Document :