DocumentCode :
3581152
Title :
Influence on zero-sequence components of autotransformer neutral grounding via small reactance in one 500kV substation
Author :
Li Xiao-hua ; Dai Meisheng ; Xie Yi-si ; Luo Long-bo ; Cai Ze-xiang
Author_Institution :
China Sch. of Electr. Power, South China Univ. of Technol., Guangzhou, China
fYear :
2014
Firstpage :
1
Lastpage :
5
Abstract :
Transformers neutral grounding accessing small reactance is an effective measure to restrain short circuit current in 500kV power grid. But accessing small reactance will bring changes to the zero-sequence parameters of system. The relay protection, especially the main transformer protection and transmission line protection nearby will be affected and act incorrectly when unsymmetrical earth fault occurs in the transmission line. An equivalent system model based on the Guangdong power grid´s actual parameter and autotransformer in 500kV substation is built, the effects on power system´s zero-sequence parameters as only one autotransformer neutral point grounded via small reactance is analyzed Meanwhile, a quantitative calculation is accomplished based on the relative variation of zero-sequence components from three aspects: fault position, resistance value and transmission line length. Furthermore, the effects on protective relaying and coordination between the adjacent lines are analyzed according to curves drawn by Matlab. Zero-sequence current protection of autotransformer neutral should be reset to meet sensitivity.
Keywords :
autotransformers; earthing; electric reactance; fault location; overvoltage protection; power grids; power transformer protection; relay protection; short-circuit currents; substation protection; China; Guangdong power grid; autotransformer neutral grounding; fault position; short circuit current; transformer protection; transmission line protection; unsymmetrical earth fault; voltage 500 kV; zero-sequence components influence; zero-sequence current protection; Circuit faults; Grounding; Impedance; Power transmission lines; Protective relaying; Short-circuit currents; Substations; branch coefficient; neutral grounding; relay protection; small reactance; zero sequence current;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Energy Engineering Conference (APPEEC), 2014 IEEE PES Asia-Pacific
Type :
conf
DOI :
10.1109/APPEEC.2014.7066168
Filename :
7066168
Link To Document :
بازگشت