DocumentCode :
358129
Title :
Phenomena of induced discharge due to static charge in transformer oil
Author :
Ji, Liu ; Shaokui, Wang ; JiaXiang, Yang
Author_Institution :
Coll. of Electr. & Electron. Eng., Harbin Univ. of Sci. & Technol., China
Volume :
2
fYear :
2000
fDate :
2000
Firstpage :
988
Abstract :
The accumulation of static charge occurs more readily in dielectric liquids, such as transformer oil, due to flowing electrification, which is potentially hazardous for utilization, storage and transportation. In this paper, the investigation of atmospheric breakdown due to static charge in transformer oil was performed using test models. The experimental results show that there is an apparent polarity effect for the induced discharge. Also, the environmental humidity, temperature and electric field structure play important roles in the induced discharge
Keywords :
discharges (electric); electric breakdown; insulation testing; power transformer insulation; static electrification; transformer oil; atmospheric breakdown; electric field structure; environmental humidity; flowing electrification; induced discharge; oil tanks; polarity effect; potential hazard; static charge; temperature effect; test models; transformer oil; Ducts; Electrodes; Fluid flow measurement; Fuel storage; Humidity; Oil insulation; Petroleum; Power transformer insulation; Power transformers; Testing;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Properties and Applications of Dielectric Materials, 2000. Proceedings of the 6th International Conference on
Conference_Location :
Xi´an
Print_ISBN :
0-7803-5459-1
Type :
conf
DOI :
10.1109/ICPADM.2000.876396
Filename :
876396
Link To Document :
بازگشت