DocumentCode
358300
Title
Metal vapor deposition on ceramic insulators and vacuum interrupter lifetime prediction
Author
Schellekens, Hans ; Battandie, Jean-Yves
Author_Institution
Schneider lectr., Grenoble, France
Volume
1
fYear
2000
fDate
2000
Firstpage
119
Abstract
A Monte Carlo approach is used to assess the deposition of metal vapour and droplets on the insulating parts of a vacuum interrupter. The model predictions are compared with a SEM analysis of sealed vacuum interrupters after interruption tests at full short circuit currents. The method presented enables electrical lifetime prediction in the design phase of the development
Keywords
Monte Carlo methods; ceramic insulators; circuit-breaking arcs; scanning electron microscopy; short-circuit currents; switchgear testing; vacuum arcs; vacuum interrupters; vapour deposition; Monte Carlo approach; SEM analysis; ceramic insulators; electrical lifetime prediction; interruption tests; metal vapor deposition; sealed vacuum interrupters; short circuit currents; vacuum interrupter lifetime prediction; Cathodes; Ceramics; Chemical vapor deposition; Circuit testing; Contacts; Dielectrics and electrical insulation; Interrupters; Metal-insulator structures; Predictive models; Vacuum arcs;
fLanguage
English
Publisher
ieee
Conference_Titel
Discharges and Electrical Insulation in Vacuum, 2000. Proceedings. ISDEIV. XIXth International Symposium on
Conference_Location
Xi´an
Print_ISBN
0-7803-5791-4
Type
conf
DOI
10.1109/DEIV.2000.877270
Filename
877270