DocumentCode :
358307
Title :
On criteria of optimized application of AMF- and RMF-contact systems in vacuum interrupters
Author :
Renz, R.
Author_Institution :
Siemens AG, Berlin, Germany
Volume :
1
fYear :
2000
fDate :
2000
Firstpage :
176
Abstract :
In case of interrupting high AC-currents in vacuum, a metal vapour arc burns between the separating contacts, till the next current-zero. However, if the current exceeds the range of approximately 10 kA the arc will pinch due to its own magnetic field. In order to avoid a local contact overheating there are two possibilities: movement of the constricted arc on the contact surface by a radial magnetic field (RMF); and prevention of arc constriction by an axial magnetic field (AMF). In this short overview the functional principles and physics of RMF and AMF are given. Pros and cons of RMF versus AMF with regard to interrupting capability, electrical resistance, tubes dimension and production costs are compared for the low, medium and high voltage range
Keywords :
circuit-breaking arcs; electric resistance; electrical contacts; magnetic fields; vacuum arcs; vacuum interrupters; arc constriction prevention; arc pinch; axial magnetic field; constricted arc movement; electrical resistance; high AC-currents interruption; local contact overheating avoidance; magnetic field; metal vapour arc; production costs; radial magnetic field; vacuum interrupters; Contacts; Electric resistance; Interrupters; Magnetic fields; Medium voltage; Physics; Production; Vacuum arcs; Vacuum systems; Vacuum technology;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Discharges and Electrical Insulation in Vacuum, 2000. Proceedings. ISDEIV. XIXth International Symposium on
Conference_Location :
Xi´an
Print_ISBN :
0-7803-5791-4
Type :
conf
DOI :
10.1109/DEIV.2000.877279
Filename :
877279
Link To Document :
بازگشت