DocumentCode :
3589147
Title :
A Lyapunov exponent based method for online transient stability assessment
Author :
Banerjee, P. ; Srivastava, S.C. ; Srivastava, K.N.
Author_Institution :
Dept. of Electr. Eng., Indian Inst. of Technol. Kanpur, Kanpur, India
fYear :
2014
Firstpage :
1
Lastpage :
6
Abstract :
The post fault transient stability of the power system is assessed in this paper using Maximum Lyapunov Exponent (MLE). The phase angles, reported by the PMUs at the generator buses are used for estimating the MLE of the system. The sign and the magnitude of the MLE serve as indicators to the stability of the system. The method utilized for estimation of the MLE is independent of the system model and is solely based on the measurement data of the system states, which can be obtained from the Phasor Measurement Units (PMUs). Different combination of fault duration and location are simulated to analyze the system stability using MLE on 3 machine 9 bus system and 10 machine New England (NE) 39 bus system.
Keywords :
Lyapunov methods; phasor measurement; power system transient stability; Lyapunov exponent based method; MLE; PMU; fault duration; fault location; fault transient stability; generator buses; maximum Lyapunov exponent; online transient stability assessment; phasor measurement units; power system; Generators; Mathematical model; Maximum likelihood estimation; Phasor measurement units; Power system stability; Stability analysis; Lyapunov Exponent; PMU measurements; Transient stability; online detection;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Systems Conference (NPSC), 2014 Eighteenth National
Type :
conf
DOI :
10.1109/NPSC.2014.7103871
Filename :
7103871
Link To Document :
بازگشت