DocumentCode :
35912
Title :
New methods of DGA diagnosis using IEC TC 10 and related databases Part 1: application of gas-ratio combinations
Author :
Sung-wook Kim ; Sung-jik Kim ; Hwang-dong Seo ; Jae-ryong Jung ; Hang-jun Yang ; Duval, Michel
Author_Institution :
HYOSUNG Corp., Changwon, South Korea
Volume :
20
Issue :
2
fYear :
2013
fDate :
Apr-13
Firstpage :
685
Lastpage :
690
Abstract :
This paper proposes a new method of DGA diagnosis, using IEC TC 10 and related databases. We analyzed five gas components (hydrogen, methane, acetylene, ethylene and ethane), which are used for analysis in the standards, with 10 types of gas ratios, and came up with 6 types of gas ratios among them, that can classify faults. Then, we reorganized and analyzed the 6 gas ratios with 15 gas-ratio combinations. From the results, we can suggest a new diagnosis method using 3 gas-ratio combinations that are able to classify fault areas clearly.
Keywords :
IEC standards; electrical faults; fault diagnosis; power transformer insulation; transformer oil; DGA diagnosis; IEC TC 10; acetylene; database; dissolved gas analysis; ethane; ethylene; fault classification; gas component; gas-ratio combination application; hydrogen; methane; Databases; Hydrogen; IEC standards; Oil insulation; Partial discharges; Power transformers; DGA diagnosis; IEC TC 10; gas ratio; new method;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/TDEI.2013.6508773