DocumentCode :
35923
Title :
New methods of DGA diagnosis using IEC TC 10 and related databases Part 2: application of relative content of fault gases
Author :
Soo-Jin Lee ; Young-Min Kim ; Hwang-dong Seo ; Jae-ryong Jung ; Hang-jun Yang ; Duval, Michel
Author_Institution :
HYOSUNG Corp., Changwon, South Korea
Volume :
20
Issue :
2
fYear :
2013
fDate :
Apr-13
Firstpage :
691
Lastpage :
696
Abstract :
Four combustible gases (hydrogen, acetylene, ethylene and methane) generated by internal faults in transformers were selected in this paper to diagnose faults, and two diagnosis methods are proposed. One consists in distinguishing between faults based on the relative percentage of these four gases, and the other in using combinations of the relative percentage of two of these four gases. Accuracy of the proposed diagnosis methods was verified using IEC TC 10 and related databases.
Keywords :
fault diagnosis; power transformers; DGA diagnosis method; IEC TC 10; acetylene; combustible gases; dissolved gas analysis; ethylene; fault gases; internal fault diagnosis method; methane; power transformer; related databases; Databases; Hydrogen; IEC standards; Oil insulation; Partial discharges; Power transformer insulation; DGA; DGA Diagnosis method; IEC TC 10;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/TDEI.2013.6508774
Filename :
6508774
Link To Document :
بازگشت