  • Abstract
    The power frequency resonance overvoltage problem of a 500kV transmission line under non-full phase operation after installation of high voltage shunt reactor is analyzed. It is pointed out that the overvoltage problem is the result of the simultaneous action of higher compensation degree of high voltage shunt reactor, untransposition of the transmission line and improper neutral reactor value of high voltage shunt reactor. Technical measure that the transmission line should be transposed and the neutral reactor value should be rechosen is proposed. An equivalent model of tower is used to ensure the accuracy of simulation. Test results after the accomplishment of the modification project show that the proposed technical measure is effective.
  • Keywords
    poles and towers; power transmission lines; reactors (electric); high voltage shunt reactor; neutral reactor value; power frequency resonance overvoltage problem; tower equivalent model; transmission line overvoltage problem analysis; voltage 500 kV; Analytical models; Capacitance; Inductors; Resonant frequency; high voltage shunt reactor; overvoltage; power frequency resonance; transmission line;