DocumentCode
3596685
Title
Analysis of ferroresonance suppression and transient response performances for various ferroresonance suppression circuits in capacitive voltage transformers
Author
Khan, Shakil Ahamed ; Bakar, A.H.A. ; Rahim, N.A. ; ChiaKwang Tan
Author_Institution
Power Energy Dedicated Adv. Centre (UMPEDAC), Univ. of Malaya, Kuala Lumpur, Malaysia
fYear
2014
Firstpage
1
Lastpage
6
Abstract
This paper presents the analysis of various ferroresonance suppression circuits (FSCs) in 132 KV Capacitive Voltage Transformers (CVTs). Simulation studies are conducted on 132 kV Trench CVT using Electro-Magnetic Transients Program (EMTP). In this paper, ferroresonance is initiated in CVT by circuit breaker switching. The ferroresonance mitigation performances of these FSC methods are then evaluated and compared. In addition, the transient response of the CVT due to power system fault is also investigated for the different types of FSC circuits. It is demonstrated in this paper that, the transient performance of CVT with electronic type FSC delivered the best results in comparison to active or passive ferroresonance mitigation circuits.
Keywords
EMTP; circuit breakers; ferroresonance; potential transformers; power system faults; CVT; EMTP; FSC methods; active ferroresonance mitigation circuits; capacitive voltage transformers; circuit breaker switching; electro-magnetic transients program; ferroresonance mitigation performances; ferroresonance suppression analysis; ferroresonance suppression circuits; passive ferroresonance mitigation circuits; power system fault; suppression circuits; transient response performances; voltage 132 kV; Ferroresonance; capacitive voltage transformer (CVT); distance relay; ferroresonance suppression circuit (FSC); transient response;
fLanguage
English
Publisher
iet
Conference_Titel
Clean Energy and Technology (CEAT) 2014, 3rd IET International Conference on
Print_ISBN
978-1-78561-069-1
Type
conf
DOI
10.1049/cp.2014.1474
Filename
7151636
Link To Document