• DocumentCode
    3597283
  • Title

    Setting Considerations of Distance Relay for UHV/EHV Long Transmission Lines

  • Author

    Su, Bin ; Wang, Jianping ; Yang, Ying ; Gong, Weixing ; Xu, Yongsheng

  • Author_Institution
    Corp. Res., ABB China Ltd., Beijing
  • fYear
    2007
  • Firstpage
    1
  • Lastpage
    7
  • Abstract
    UHV/EHV long transmission lines have large distributed capacitance and small shunt reactors, both of which have comparable impedance with the line impedance, therefore have significant effects on the operation of a distance relay. To set the distance relay without considering any of the above two factors will cause serious overreaching or underreaching. This paper analyzes the effect of distributed capacitance and shunt reactors on the apparent impedance of a distance relay, and therefore points out the setting principles of distance relay for UHV/EHV long transmission lines. Plenty of EMTDC simulations have proved that the analysis results are correct and the setting principles can ensure the reliability and selectivity of the distance relay for UHV/EHV long transmission lines.
  • Keywords
    capacitance; electric reactance; high-voltage techniques; power transmission lines; power transmission protection; relay protection; transmission network calculations; EHV long transmission lines; EMTDC simulation; UHV long transmission lines; apparent impedance; distance relay; distributed capacitance; setting consideration; shunt reactor; Analytical models; Capacitance; Impedance; Inductors; Power system reliability; Power transmission lines; Protection; Protective relaying; Shunt (electrical); Transmission lines; distance relay; distributed capacitance; shunt reactor; transmission line;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Society General Meeting, 2007. IEEE
  • ISSN
    1932-5517
  • Print_ISBN
    1-4244-1296-X
  • Electronic_ISBN
    1932-5517
  • Type

    conf

  • DOI
    10.1109/PES.2007.385557
  • Filename
    4275439