DocumentCode :
3602026
Title :
Optimal Operation of Distribution Networks Considering Energy Storage Devices
Author :
Macedo, Leonardo H. ; Franco, John F. ; Rider, Marcos J. ; Romero, Ruben
Author_Institution :
Dept. de Eng. Eletr., Univ. Estadual Paulista, Sao Paulo, Brazil
Volume :
6
Issue :
6
fYear :
2015
Firstpage :
2825
Lastpage :
2836
Abstract :
This paper presents a mixed-integer second-order cone programing (MISOCP) model to solve the optimal operation problem of radial distribution networks (DNs) with energy storage. The control variables are the active and reactive generated power of dispatchable distributed generators (DGs), the number of switchable capacitor bank units in operation, the tap position of the voltage regulators and on-load tap-changers, and the operation state of the energy storage devices. The objective is to minimize the total cost of energy purchased from the distribution substation and the dispatchable DGs. The steady-state operation of the DN is modeled using linear and second-order cone programing. The use of an MISOCP model guarantees convergence to optimality using existing optimization software. A mixed-integer linear programing (MILP) formulation for the original model is also presented in order to show the accuracy of the proposed MISOCP model. An 11-node test system and a 42-node real system were used to demonstrate the effectiveness of the proposed MISOCP and MILP models.
Keywords :
energy storage; integer programming; linear programming; power distribution control; power system simulation; reactive power control; MILP formulation; MISOCP model; dispatchable distributed generators; distribution substation; energy storage devices; linear cone programing; mixed-integer linear programing; mixed-integer second-order cone programming; on-load tap-changers; optimal operation problem; optimization software; radial distribution networks; reactive generated power control; steady-state operation; switchable capacitor bank units; voltage regulators; Distributed power generation; Energy storage; Mixed integer linear programming; Reactive power; Distributed generation; energy storage; mixed-integer linear programing (MILP); mixed-integer second-order cone programing (MISOCP); optimal operation of radial distribution networks; smart grid;
fLanguage :
English
Journal_Title :
Smart Grid, IEEE Transactions on
Publisher :
ieee
ISSN :
1949-3053
Type :
jour
DOI :
10.1109/TSG.2015.2419134
Filename :
7095593
Link To Document :
بازگشت