DocumentCode :
3602739
Title :
Snubber Circuit Design for Transformers in an Urban High Rise Office Building
Author :
Sutherland, Peter E.
Author_Institution :
Ind. Solutions, GE Energy, Rotterdam, NY, USA
Volume :
51
Issue :
6
fYear :
2015
Firstpage :
4347
Lastpage :
4356
Abstract :
Transformer failures have in recent years led to the development of resistor-capacitor snubber circuits for the protection of the transformer and winding insulation from the damaging effects of high-voltage high-frequency transients. Transformer insulation may be damaged if the basic insulation level is exceeded, during turn-to-turn insulation, when there is excessive rate of change of voltage with time (dv/dt), and in switching devices by restrikes when the transient recovery voltage is exceeded. These transients are most often observed when dry-type transformers are closely coupled to vacuum switching devices. Some manufacturers are now including snubbers in their transformer designs. This paper provides a thorough review of the causes of the transients, methods of analysis, and mitigation of the effects of these transients. An example is provided of transformers to be installed in the basement of an urban high rise office building (where the space is limited and the available fault current is high), where the transformer enclosure includes built-in snubber circuits. The strengths and weaknesses of current methods are examined. Recommendations are made for improvements in snubber circuit design and analysis.
Keywords :
building management systems; snubbers; transformer insulation; dry-type transformers; high-voltage high-frequency transients; snubber circuit design; transformer insulation; transient recovery voltage; urban high rise office building; Cable insulation; Cable shielding; Power cables; Power transformer insulation; Snubbers; Transient analysis; Snubbers; Transformer failure; Transformer protection; Transformer snubber circuits; Transient analysis; Transient overvoltages; Transient rate of rise of voltage; transformer failure; transformer protection; transformer snubber circuits; transient analysis; transient overvoltages; transient rate of rise of voltage;
fLanguage :
English
Journal_Title :
Industry Applications, IEEE Transactions on
Publisher :
ieee
ISSN :
0093-9994
Type :
jour
DOI :
10.1109/TIA.2015.2440357
Filename :
7116555
Link To Document :