Title :
Voltage booster scheme for enhancing the fault ride-through of wind turbines
Author :
Goweily, Khaled ; El Moursi, Mohamed Shawky ; Abdel-rahman, Mohamed ; Badr, Mohamed A. L.
Author_Institution :
Electr. Power & Machines Eng. Dept., Ain Shams Univ., Cairo, Egypt
Abstract :
This study presents a new scheme for a continuously variable (CV) series braking resistor (SBR) with independent per phase controller. The CV-SBR is a CV and not stepwise. A novelty of the work presented is that the CV-SBR operates on the whole range of wind speeds. The proposed scheme is applicable to fault ride-through (FRT) of fixed speed wind turbines (FSWTs). The CV-SBR scheme is compared to the single-step (SS) and multi-steps (MS) SBRs. The CV-SBR scheme is modelled and simulated in PSCAD/EMTDC™. The performance of the wind turbine is studied for balanced and unbalanced fault scenarios. The CV-SBR scheme is advantageous over the other two candidates with its ability to limit the fault current and reduce the turbine speed deviation at any wind speed. The CV-SBR is employed with a static synchronous compensator (STATCOM) to allow FRT of FSWT connected to weak grid during nearby faults and to deliver the reactive current required by some grid codes. The CV-SBR scheme is successful in reducing voltage disturbance´s consequences on the generator´s mechanical system. Simulation results show that the CV-SBR allows FRT of FSWT connected to weak grid where the STATCOM alone is not able to sufficiently enhance the FRT of FSWT during nearby faults.
Keywords :
angular velocity control; braking; fault currents; machine control; phase control; power grids; power system faults; static VAr compensators; turbogenerators; wind turbines; CV SBR; FSWT; PSCAD/EMTDC; STATCOM; continuously variable series braking resistor; fault current limiting; grid side; phase controller; phase voltage magnitude; reactive current; static synchronous compensator; turbine speed deviation reduction; voltage booster scheme; voltage disturbance reduction; wind speed control; wind turbine FRT; wind turbine generator fault ride-through enhancement;
Journal_Title :
Power Electronics, IET
DOI :
10.1049/iet-pel.2014.0548